In the winter and spring of 2023/24, BTS measured the U-value of a solid masonry wall in a detached 4 bedroom house in Berkshire, UK, before and after the application of Build with Hemp Insulation Mats. Following the application of the insulation the U-value of the wall reduced from 2.01W/m2K to 0.40W/m2K, a performance improvement of 80% which was slightly higher than the expected improvement of 72%. This provides a successful demonstration that the Build with Hemp Insulation Mats deliver the laboratory-measured in a real world application.
The U-value measurements were carried out using heat flux plates according to the method set out in ISO9869-1:20141, U-value measurements using BTS’ Heat3D equipment2.
The Results
The pre-retrofit measurements showed that the house had high heat loss through the walls, consistent with a solid masonry wall construction. The retrofit measure was to install 50mm of Build with Hemp’s Hemp Insulation Mats, which have a listed thermal conductivity of 0.039W/mK. The expected effect of the insulation on the wall’s U-value was calculated given the measured pre-retrofit performance, resulting in a design expectation for the wall of 0.56W/m2K.
The post-retrofit U-value measurement was significantly lower, demonstrating a clear thermal performance improvement. The anticipated effect of the retrofit was in fact slightly exceeded, this could be due to better than expected performance of the insulation or an unventilated air gap being introduced somewhere in the construction. The measurements, therefore, provide a successful demonstration that the manufacturer’s listed performance was delivered in a real-world installation.
The Measurement Methods
U-values of elements have traditionally been measured using heat flux plates, these are sensors about the size of a coaster and measure the heat flux passing through them. By attaching them to the surface of a building element (e.g. wall, floor or ceiling) the amount of heat flux through that element can be measured, and by measuring the temperature on either side of the element the U-value of that element can be calculated according to the method set out in ISO9869-1:2014. This method requires that the heat flux plates be left in place for at least 3 days in order for the measurement to be valid, this is to check that the measurement is of the heat transfer through the wall, rather than heat storage within it.
One drawback of using heat flux plates to measure U-values is that they only measure over a very small area compared to the typical size of a building element, this means that if the U-value is variable across the surface it will not be detected by the measurement. To address this, BTS manufacture a product called Heat3D that uses infrared imaging so that the U-value of whole surfaces can be measured at once.